The GMP232/x2 enables the safe, reliable and fast measurement of all relevant values for three-phase electrical networks. It also provides a number of monitoring functions for generator and grid protection. Up to 2 circuitbreakers/trip circuits are triggered by the module directly via relay outputs. The continuous monitoring of grid harmonics up to the 50th harmonic can be used for direct reactions as well as for evaluating the power quality.

The module is provided with an integrated real-time data recorder for the high-precision recording of up to 24 measuring channels during alarm/protection events. Error events are recorded continuously and stored with a high resolution time stamp. The internal time base of the module can be synchronized to an external time source (e.g. IEEE 1588 Precision Time Protocol), which supports the analysis of the data from geographically separated measurement and protection devices.

The GMP232/x2 module is fully integrated in the Bachmann SolutionCenter. Configurations can be created simply and stored for later reuse. Both the measured channel values and also the derived values are made available directly in the user interface. Commissioning and fault analysis are simplified with tabular, vector and time sequence displays. Event logs and recorded time sequences can be exported in CSV resp. COMTRADE format. The integrated simulation function simplifies the configuration of protection and monitoring functions.

 

Features

  • Measurement of current, voltage, frequency, power, power factor, phase angle
  • Direct connection up to 1000 Vrms rated CAT III
  • True RMS and fundamental RMS, symmetrical components
  • High dynamic measurement / very low latency
  • Measurement of grid harmonics up to the 50th (PQ)
  • Configurable grid and generator protection
  • Direct relay outputs for circuit-breaker/trip circuits
  • Integrated real-time fault recording
  • Integrated event logging
  • 4Q energy meter
  • Integrated mean value aggregation, grid statistics
  • Measured value simulation

Approvals / Certificates

Declaration of Conformity

CE

Communauté Européenne

UK

United Kingdom

UL

Underwriters Laboratories

Generator Grid Connection

GER

VDE-AR-N 4110 / VDE-AR-N 4120 / FGW TR3 / FGW TR8

CENELEC

EN 50549-2

UK

ENA G99/1/9

USA

IEEE C37.90

Maritime & Offshore

ABS 

American Bureau Of Shipping

BV

Bureau Veritas

DNV 

Det Norske Veritas

LR 

Lloyds Register

KR 

Korean Register

NK 

Nippon Kaiji Kyokai

RINA 

Registro Italiano Navale

 

Here you will find the download section for certificates and approvals: Certificates